This is the Fike 204-0012 Twinflex ASD Multipoint detector complete with sounder and strobe, which can be used as a smoke, heat, or multisensor detector. It comes complete with the base plate. Multifunction smoke and heat detector with seven detection modes, ideal for the Fike Twinflex Pro range of 2-wire fire alarm control panels.
Note: this item is non-returnable; we are not able to take it back as “unwanted”. Please make sure that this is the exact item you require before ordering.
The Twinflex Multipoint ASD is a plug-in type smoke detector that utilises a photo-electric sensing chamber to make a measurement corresponding to smoke density. The device also incorporates a thermistor sensing circuit to allow for accurate heat measurement. These elements allow the device to be configured to a smoke, heat or combined setting. This device is only compatible with the Twinflex control panels (and their associated detection and alarm equipment) and also incorporates a sounder beacon.
7 modes of detection: 3 x smoke detection modes, 3 x heat detection modes, and 1 x combination mode. You can select your required option using the in-built DIL switches located within the detector.
Fike 204-0003 Twinflex Multipoint ASD Detector – Features
- Part of the Twinflex Pro intelligent 2-wire fire alarm system.
- Complete with a built-in sounder and a mounting plate.
- Self-calibrates every 6h.
- Continuously monitors for dust contamination.
- Can be used as a smoke detector, a heat detector, or a multi-sensor.
Fike 204-0003 Multipoint Detector – Technical Data
- Dimensions: 107mm diameter x 75mm
- Operating temperature: -10 deg C to +50 deg C
- Operating Voltage Range: 18V to 32V DC
- Operating Current Quiescent: 109 uA (Typical)
- End of line ON if applicable: +50 uA (Typical)
- Alarm Sounding Sounder High: 10.54 mA (Typical)
- Alarm Sounding Sounder Low: 4.92 mA (Typical)
- Alarm Sounding Sounder Off: 2.58 mA (Typical)
- Alarm Activated: 17.92 mA (Typical) (in addition to Alarm Sounding)
- LED Operation Detector in Normal State (Smoke): Flash at 20 second intervals
- Detector in Normal State (Heat): Double flash at 20 second intervals
- Detector at EOL: Flash at 5 second intervals
- Detector in Fault: Flash at 1.3 second intervals
- Detector Detecting Fire: Flash at 0.7 second intervals
- Detector in Fire (once processed at panel): Continuous
- Sounder High: 2.0 SLU (V3 panel), 10.5 DLU (Pro panel)
- Sounder Low: 1.0 SLU(V3 panel), 5.0 DLU (Pro panel)
- No Sounder: 0.5 SLU(V3 panel), 3.0 DLU (Pro panel)
- Volume Level (@ 1m anechoic, Dual Tone): Sounder High: 90+ dB(A), Sounder Low: 70+ dB(A)
- Flammability: UL94-V2
- IP Rating: IP 21 rated
Note: picture is for information purposes only.
Fire Alarm Specs | |
Alarm Type | Multi-Sensor (Heat and Smoke) |
Battery Back-up | No |
Brand | Fike |
Interconnection | Wired |
Location | Ceiling |
Operating Temperature | up to 50deg C |
Sensor Type | Smoke and Heat Detector |
Smart Features | None |
Sound Level | 70 – 90db |
Voltage | 16 – 48V DC |